Description
APPLICATIONS
Toxfree® Marine XTCuZ1-K (AS) - halogen-free, lined cable is a safety cable. In case of fire, it does not release toxic or corrosive gases, protecting human health and preventing possible damage to electronic equipment. For this reason, its use is recommended for marine applications. VFD (Variable Frequency Drive) use: thanks to its special shielding, it is suitable for installations where high-frequency electromagnetic interference from nearby circuits must be avoided.
• For marine use.
STRUCTURE
Conductor
Electrolytic annealed copper conductor, class 5 (flexible), according to standards EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene insulation, type HF XLPE-90 °C, according to standard IEC 60092-360. The standard identification of insulated conductors according to HD 308 is as follows:
1 x natural
3 x brown + black + gray
4 x brown + black + gray + blue
Other colors available on request.
Bedding
Thermoplastic polyolefin, natural color, low smoke and halogen-free in case of fire.
Shielding
Aluminum-polyester tape shield + overlapping tinned copper braid shield, ensuring 100% shielding.
Outer sheath
Low smoke halogen-free (LSHF) thermoplastic polyolefin sheath, type SHF1, according to standard IEC 60092-360. Black color.
DIMENSIONS AND LOAD CAPACITIES
| Cross-section (mm²) |
Diameter (mm) |
Weight (kg/km) |
Outdoor (A) 1 |
Resistance at 20ºC (Ω/km) |
Voltage drop (V/A · km) 2 |
|---|---|---|---|---|---|
| 1 x 70 | 20,5 | 975 | 233 | 0,272 | 0,603 |
| 1 x 95 | 22,3 | 1.215 | 285 | 0,206 | 0,457 |
| 1 x 185 | 27,7 | 2.075 | 444 | 0,106 | 0,235 |
| 1 x 300 | 33,0 | 3.270 | 612 | 0,0641 | 0,142 |
| 3 x 95 | 42,5 | 4.005 | 259 | 0,206 | 0,457 |
| 3 x 120 | 46,6 | 4.925 | 301 | 0,161 | 0,357 |
| 3 x 150 | 50,3 | 5.935 | 347 | 0,129 | 0,286 |
| 3 x 185 | 54,3 | 7.035 | 397 | 0,106 | 0,235 |
| 3 x 240 | 60,9 | 9.030 | 468 | 0,0801 | 0,178 |
| 3 x 300 | 66,3 | 11.155 | 540 | 0,0641 | 0,142 |
¹ Reference method F for single-core and method E for multicore cables according to IEC 60092-352 in open air at 45°C ambient temperature.
² At maximum service temperature and cosf=1.
For cables having 2 conductors and 3 conductors up to 10 mm², it is supposed a single-phase circuit. For the rest of the cables it is supposed a three-phase circuit.