TOXFREE® MARINE PLUS XZ1-K (AS+) Armoured fire-resistant marine cable

Description

APPLICATIONS

Toxfree® Marine Plus XZ1-K (AS+) is specifically designed for electrical transmission during a fire, ensuring power supply to emergency circuits such as indicator lights, smoke extraction systems, audible alarms, water pumps, etc. In the event of a fire, it does not release toxic or corrosive gases, thus protecting human health and preventing potential damage to electronic equipment. For this reason, its use is recommended for public spaces and marine applications.

• For marine use.

• For public use.

STRUCTURE

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to standards EN 60228 and IEC 60228.

Insulation

Mica tape + cross-linked polyethylene insulation, type HF XLPE 90 °C, according to standard IEC 60092-360.

Standard identification according to HD 308 is as follows:

1 x natural

2 × blue + brown

3 x brown + black + gray

4 x brown + black + gray + blue

5 or more conductors: black, numbered

Other colors available on request.

Outer sheath

Low Smoke Halogen Free (LSHF) thermoplastic polyolefin sheath, type SHF1, according to IEC 60092-360. Orange color, non-toxic, flame retardant and fire resistant.

DIMENSIONS AND LOADABLE

Cross-section area (mm²) Diameter (mm) Weight (kg/km) Outdoor (A) Voltage drop (V/A · km) Resistance at 20ºC (Ω/km)
1 x 2.5 5,9 51 25 17,7 7,98
1 x 4 6,4 68 35 11,0 4,95
1 x 6 7,0 89 46 7,32 3,3
1 x 10 7,9 133 64 4,23 1,91
1 x 16 9,1 195 88 2,68 1,21
1 x 25 10,9 290 117 1,73 0,78
1 x 35 12,2 393 147 1,23 0,554
1 x 50 13,9 540 180 0,86 0,386
1 x 70 15,8 741 233 0,60 0,272
1 x 95 17,9 969 285 0,46 0,206
1 x 120 19,5 1.212 333 0,36 0,161
1 x 150 21,8 1.504 386 0,29 0,129
1 x 185 24,4 1.828 444 0,24 0,106
1 x 240 27,4 2.379 528 0,18 0,0801
1 x 300 30,1 2.981 612 0,14 0,0641
2 x 1.5 9,2 121 23 34,0 13,3
2 x 2,5 10,1 154 31 20,4 7,98
2 x 4 11,4 209 43 12,7 4,95
2 x 6 12,4 266 55 8,45 3,3
2 x 10 14,5 395 75 4,89 1,91
2 x 16 16,1 542 100 3,10 1,21
3 x 1.5 10,0 140 23 34,0 13,3
3 x 2.5 11,0 186 31 20,4 7,98
3 x 4 12,2 247 43 12,7 4,95
3 x 6 13,3 321 55 8,45 3,3
3 x 10 15,7 489 75 4,89 1,91
3 x 16 17,9 701 87 2,68 1,21
3 x 25 22,3 1.097 110 1,73 0,78
3 x 35 25,3 1.470 137 1,23 0,554
3 x 50 28,9 2.013 167 0,86 0,386
3 x 70 31,6 2.677 214 0,60 0,272
3 x 95 37,7 3.575 259 0,46 0,206
3 x 120 41,5 4.480 301 0,36 0,161
3 x 150 46,4 5.566 347 0,29 0,129
3 x 185 52,0 6.806 397 0,24 0,106
3 x 240 58,4 8.813 468 0,18 0,0801
4 x 1.5 11,1 170 20 29,5 13,3
4 x 2.5 12,0 221 28 17,7 7,98
4 x 4 13,3 298 37 11,0 4,95
4 x 6 14,9 400 47 7,32 3,3
4 x 10 17,4 609 65 4,23 1,91
4 x 16 20,1 883 87 2,68 1,21
4 x 25 25,1 1.379 110 1,73 0,78
4 x 35 27,3 1.820 137 1,23 0,554
4 x 50 32,7 2.558 167 0,86 0,386
4 x 70 37,0 3.467 214 0,60 0,272
4 x 95 42,0 4.524 259 0,46 0,206
4 x 120 46,2 5.675 301 0,36 0,161
4 x 150 51,6 7.083 347 0,29 0,129
4 x 185 57,9 8.654 397 0,24 0,106
4 x 240 65,1 11.243 468 0,18 0,0801
5 x 1.5 12,0 199 20 29,5 13,3
5 x 2.5 13,2 264 28 17,7 7,98
5 x 4 14,9 364 37 11,0 4,95
5 x 6 16,6 490 47 7,32 3,3
5 x 10 19,3 747 65 4,23 1,91
5 x 16 22,4 1.088 87 2,68 1,21
7 x 1.5 12,9 240 11 29,5 13,3
7 x 2,5 14,7 334 15 17,7 7,98
10 x 1.5 15,6 337 10 29,5 13,3
12 x 1,5 16,6 395 9 29,5 13,3
12 x 2.5 19,5 561 12 17,7 7,98
14 x 1.5 17,8 394 9 29,5 13,3
16 x 1,5 19,2 454 8 29,5 13,3
19 x 1.5 20,0 514 8 29,5 13,3
19 x 2.5 23,0 730 11 17,7 7,98
24 x 1,5 22,7 640 7 29,5 13,3
27 x 1.5 24,0 709 7 29,5 13,3
27 x 2.5 27,8 1.023 9 17,7 7,98

¹ Reference method F for single-core and method E for multicore cables according to IEC 60092-352 in open air at 45°C ambient temperature.

² At maximum service temperature and cosf=1.

For cables having 2 conductors and 3 conductors up to 10 mm², it is supposed a single-phase circuit. For cables having more of 5 conductors is supposed that all are loaded. For the rest of the cables it is supposed a three-phase circuit.

More information

Electrical properties

Low voltage: 0.6/1 kV.

Thermal properties

Maximum operating temperature: 90 °C.
Maximum short-circuit temperature: 250 °C (max. 5 s).
Minimum operating temperature: -40 °C (in fixed installations).
Minimum installation temperature: -15 °C.

Fire performance

No flame propagation according to standards EN 60332-1 / IEC 60332-1.
No flame propagation according to EN 60332-3-22 / IEC 60332-3-22 standards.
Fire resistant according to standards EN 60331-2 (overall diameter ≤ 20 mm) and IEC 60331-1
(overall diameter > 20 mm).
LSHF (Low Smoke Halogen Free) according to standards EN 60754-1 / IEC 60754-1.
Low smoke emission according to standards EN 61034 / IEC 61034:
light transmission > 60 %.
Low emission of corrosive gases according to standards EN 60754-2 / IEC 60754-2
according to.

Mechanical properties

Minimum bending radius:
≤ 25 mm: 4 × cable diameter
25 mm: 6 × cable diameter
Impact resistance: AG2, medium stress level.

Environmental characteristics

Chemical and oil resistance: good.
UV resistant according to standard EN 50618.
Water resistance: AD6 (wave exposure).

Installation conditions

In the open air.
In conduit installed in bulkhead.
Installed in bulkhead.

STANDARDS

According to standard
IEC 60092-353

Standards and approvals
ABS / DNV-GL / BUREAU VERITAS / LLOYD’S
REGISTER / CE / RoHS