TOXFREE® MARINE XTCuZ1-K (AS) Marine power cable

Description

APPLICATION

Toxfree® Marine XTCuZ1-K (AS) halogen-free cable is a safety cable. In case of fire, it does not release toxic or corrosive gases, protecting human health and preventing possible damage to electronic equipment. For this reason, its use is recommended for marine applications.

• For marine use.

STRUCTURE

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to standards EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene insulation, type HF XLPE-90 °C, according to standard IEC 60092-360. The standard identification of insulated conductors according to HD 308 is as follows:

1 x natural

2 × blue + brown

3 x brown + black + gray

4 x brown + black + gray + blue

5 or more conductors: black, numbered

Other colors available on request.

Bedding

Thermoplastic polyolefin, natural color, low smoke and halogen-free in case of fire (for single-core and multi-core cables from 25 mm²).

Shielding

Aluminum-polyester tape shield + overlapping tinned copper braid shield, ensuring 100% shielding.

Outer sheath

Low smoke halogen-free (LSHF) thermoplastic polyolefin sheath, type SHF1, according to standard IEC 60092-360. Black color.

DIMENSIONS AND LOAD CAPACITIES

Cross-section
(mm²)
Diameter
(mm)
Weight
(kg/km)
Outdoor
(A) 1
Resistance at 20ºC
(Ω/km)
Voltage drop
(V/A · km) 2
1 x 2.5 8,2 110 25 7,98 17,7
1 x 4 8,9 135 35 4,95 11,0
1 x 6 9,5 160 46 3,30 7,32
1 x 10 10,5 215 64 1,91 4,23
1 x 16 11,5 275 88 1,21 2,68
1 x 25 13,4 385 117 0,78 1,73
1 x 35 14,3 490 147 0,554 1,23
1 x 50 16,7 680 180 0,386 0,860
1 x 70 18,7 900 233 0,272 0,603
1 x 95 20,2 1.125 285 0,206 0,457
1 x 120 22,4 1.400 333 0,161 0,357
1 x 150 24,3 1.700 386 0,129 0,286
1 x 185 26,4 2.020 444 0,106 0,235
1 x 240 29,5 2.585 528 0,0801 0,178
1 x 300 32,6 3.245 612 0,0641 0,142
1 x 400 37,7 4.240 716 0,0486 0,108
1 x 630 47,3 7.045 947 0,0287 0,064
2 x 1.5 8,6 115 23 13,3 34,0
2 x 2,5 9,5 135 31 7,98 20,4
2 x 4 10,7 180 43 4,95 12,7
2 x 6 11,3 220 55 3,3 8,45
2 x 10 15,3 475 75 1,91 4,89
2 x 16 17,3 630 100 1,21 3,1
3 x 1.5 9,1 135 23 13,3 34,0
3 x 2.5 10,0 170 31 7,98 20,4
3 x 4 11,4 225 43 4,95 12,7
3 x 6 12,4 285 55 3,3 8,45
3 x 10 15,5 475 75 1,91 4,89
3 x 16 17,7 655 87 1,21 2,68
3 x 25 22,1 1.120 110 0,78 1,73
3 x 35 24,6 1.470 137 0,554 1,23

 

Cross-section
(mm²)
Diameter
(mm)
Weight
(kg/km)
Outdoor
(A) 1
Resistance at 20ºC
(Ω/km)
Voltage drop
(V/A · km) 2
3 x 50 28,7 2.005 167 0,386 0,860
3 x 70 32,1 2.685 214 0,272 0,603
3 x 95 36,2 3.445 259 0,206 0,457
3 x 120 41,1 4.450 301 0,161 0,357
3 x 150 45,7 5.470 347 0,129 0,286
3 x 185 50,6 6.620 397 0.106 0,235
3 x 240 57,2 8.565 468 0,0801 0,178
4 x 1.5 9,9 155 20 13,3 29,5
4 x 2.5 10,9 205 28 7,98 17,7
4 x 4 12,4 275 37 4,95 11,0
4 x 6 13,8 405 47 3,3 7,32
4 x 10 17,1 585 65 1,91 4,23
4 x 16 19,9 840 87 1,21 2,68
4 x 25 24,7 1.400 110 0,78 1,73
4 x 35 26,5 1.825 137 0,554 1,23
4 x 50 32,3 2.530 167 0,386 0,860
4 x 70 36,1 3.400 214 0,272 0,603
4 x 95 40,8 4.475 259 0,206 0,457
4 x 120 46,2 5.635 301 0,161 0,357
4 x 150 50,7 6.955 347 0,129 0,286
4 x 185 56,2 8.415 397 0,106 0,235
4 x 240 63,7 10.920 468 0,0801 0,178
5 x 1.5 10,9 190 20 13,3 29,5
5 x 2.5 12,1 245 28 7,98 17,7
5 x 4 14,3 385 37 4,95 11,0
5 x 6 15,7 480 47 3,3 7,32
5 x 10 18,6 710 65 1,91 4,23
5 x 16 21,8 1.020 87 1,21 2,68
5 x 25 27,0 1.700 110 0,78 1,73
5 x 35 29,6 2.235 137 0,554 1,23
5 x 50 35,2 3.065 167 0,386 0,860
7 x 1.5 11,5 230 11 13,3 29,5
7 x 2,5 13,8 360 15 7,98 17,7
12 x 1,5 15,2 405 9 13,3 29,5
12 x 2.5 16,6 530 12,5 7,98 17,7

¹ Reference method F for single-core and method E for multicore cables according to IEC 60092-352 in open air at 45°C ambient temperature.

² At maximum service temperature and cosf=1.

For cables having 2 conductors and 3 conductors up to 10 mm², it is supposed a single-phase circuit. For cables having more of 5 conductors is supposed that all are loaded. For the rest of the cables it is supposed a three-phase circuit.

More information

Electrical properties

Low voltage: 0.6/1 kV.

Thermal properties

Maximum operating temperature: 90 °C.
Maximum short-circuit temperature: 250 °C (max. 5 s).
Minimum installation temperature: -15 °C.
Minimum operating temperature: -40 °C (in fixed and protected installations).

Fire performance

No flame propagation according to standards EN 60332-1 / IEC 60332-1.
No flame propagation according to EN 60332-3-22 / IEC 60332-3-22 standards.
LSHF (Low Smoke Halogen Free) according to standards EN 60754-1 / IEC 60754-1.
Low smoke emission according to standards EN 61034 / IEC 61034:
light transmission > 60 %.
Low emission of corrosive gases according to standards EN 60754-2 / IEC 60754-2
according to.

Mechanical properties

Minimum bending radius: 6 × cable diameter.
Impact resistance: AG3, high stress level.

Environmental characteristics

Chemical and oil resistance: acceptable.
UV resistant according to standard EN 50618.
Water resistance: AD6 (wave exposure).

Installation conditions

In the open air.
In conduit, installed on bulkhead
Installed on bulkhead

STANDARDS

According to standard
IEC 60092-353

Standards and approvals
ABS / DNV-GL / BUREAU VERITAS / LLOYD’S REGISTER /
CE / RoHS