OtsoSmart Logo White


TOXFREE® MARINE PLUS XTCuZ1-K (AS+) Armoured fire-resistant marine power cable

Description

APPLICATIONS

Toxfree® Marine Plus XTCuZ1-K (AS+) is specially designed for electrical transmission during a fire, ensuring power supply to emergency circuits such as indicator lights, smoke extraction systems, audible alarms, water pumps, etc. In the event of a fire, it does not release toxic or corrosive gases, thus protecting human health and preventing potential damage to electronic equipment. For this reason, its use is recommended in public spaces and for marine applications.

• For marine use.

• For public use.

STRUCTURE

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to standards EN 60228 and IEC 60228.

Insulation

Mica tape + cross-linked polyethylene insulation, type HF XLPE 90 °C, according to standard IEC 60092-360.

Standard identification according to HD 308 is as follows:

1 x blue + brown

2 × brown + black + grey

3 × brown + black + grey + blue

4 or more conductors: black, numbered

Other colors available on request.

Bedding

Thermoplastic polyolefin, natural color, low smoke and halogen-free in case of fire (for single-core and multi-core cables from 25 mm²).

Shielding

Aluminum-polyester tape shield + overlapping tinned copper braid shield, ensuring 100% shielding.

Outer sheath

Low Smoke Halogen Free (LSHF) thermoplastic polyolefin sheath, type SHF1, according to IEC 60092-360. Orange color, non-toxic, flame retardant and fire resistant.

DIMENSIONS AND LOAD CAPACITIES

Cross-section
(mm²)
Diameter
(mm)
Weight
(kg/km)
Outdoor
(A)
Voltage drop
(V/A · km)
Resistance at 20ºC
(Ω/km)
1 x 16 11,8 240 88 2,68 1,21
1 x 35 15,1 562 147 1,23 0,554
1 x 70 19,1 920 233 0,60 0,272
1 x 95 20,7 1.055 285 0,46 0,206
1 x 120 23,1 1.420 333 0,36 0,161
1 x 150 25,1 1.620 386 0,29 0,129
1 x 185 27,2 2.045 444 0,24 0,106
1 x 240 29,8 2.610 528 0,18 0,0801
1 x 300 32,9 3.275 612 0,14 0,0641
2 x 1.5 10,3 130 23 34,0 13,3
2 x 2,5 10,4 150 31 20,4 7,98
2 x 4 11,9 191 43 12,7 4,95
2 x 6 12,9 239 55 8,45 3,3
2 x 10 15,4 379 75 4,89 1,91
2 x 16 17,2 515 100 3,1 1,21
3 x 1.5 10,4 144 23 34,0 13,3
3 x 2.5 11,5 187 31 20,4 7,98
3 x 4 12,6 242 43 12,7 4,95
3 x 6 14,3 345 55 8,45 3,3
3 x 10 16,7 504 75 4,89 1,91
3 x 16 18,7 693 87 2,68 1,21
3 x 25 23,2 1.175 110 1,73 0,78
3 x 35 26,4 1.550 137 1,23 0,554
3 x 50 29,6 2.065 167 0,86 0,386
3 x 70 33,9 2.845 214 0,60 0,272
3 x 95 37,8 3.560 259 0,46 0,206
3 x 120 43,2 4.595 301 0,36 0,161
3 x 150 47,4 5.605 347 0,29 0,129
3 x 185 52,3 6.765 397 0,24 0,106
3 x 240 57,8 8.645 468 0,18 0,0801
4 x 1.5 11,2 180 20 29,5 13,3
4 x 2.5 11,9 225 28 17,7 7,98
4 x 4 13,3 295 37 11,0 4,95
4 x 6 15,4 435 47 7,32 3,3
4 x 10 17,9 615 65 4,23 1,91
4 x 16 20,5 865 87 2,68 1,21
4 x 25 26,2 1.475 110 1,73 0,78
4 x 35 28,4 1.915 137 1,23 0,554
4 x 70 38,9 3.630 214 0,60 0,272
4 x 120 47,8 5.765 301 0,36 0,161
4 x 185 58,1 8.555 397 0,24 0,106
4 x 240 64,4 10.990 468 0,18 0,0801
5 x 1.5 12,4 210 20 29,5 13,3
5 x 2.5 14,2 308 28 17,7 7,98
5 x 4 15,2 405 37 11,0 4,95
5 x 6 16,8 505 47 7,32 3,3
5 x 10 19,6 740 65 4,23 1,91
5 x 16 22,5 1.055 87 2,68 1,21
7 x 1.5 13,2 265 11 29,5 13,3
7 x 2,5 14,8 375 15 17,7 7,98
10 x 1.5 16,9 400 10 29,5 13,3
12 x 1,5 17,3 460 9 29,5 13,3
12 x 2.5 19,4 585 12 17,7 7,98
14 x 1.5 18,6 520 9 29,5 13,3
19 x 1.5 21,1 650 8 29,5 13,3
19 x 2.5 22,7 840 11 17,7 7,98
24 x 1,5 23,3 795 7 29,5 13,3

¹ Reference method F for single-core and method E for multicore cables according to IEC 60092-352 in open air at 45°C ambient temperature.

² At maximum service temperature and cosf=1.

For cables having 2 conductors and 3 conductors up to 10 mm², it is supposed a single-phase circuit. For cables having more of 5 conductors is supposed that all are loaded. For the rest of the cables it is supposed a three-phase circuit.

More information

Electrical properties

Low voltage: 0.6/1 kV.

Thermal properties

Maximum operating temperature: 90 °C.
Maximum short-circuit temperature: 250 °C (max. 5 s).
Minimum operating temperature: -40 °C (in fixed installations).
Minimum installation temperature: -15 °C.

Fire performance

No flame propagation according to standards EN 60332-1 / IEC 60332-1.
No flame propagation according to EN 60332-3-22 / IEC 60332-3-22 standards.
Fire resistant according to standards EN 60331-2 (overall diameter ≤ 20 mm) and IEC 60331-1
(overall diameter > 20 mm).
LSHF (Low Smoke Halogen Free) according to standards EN 60754-1 / IEC 60754-1.
Low smoke emission according to standards EN 61034 / IEC 61034:
light transmission > 60 %.
Low emission of corrosive gases according to standards EN 60754-2 / IEC 60754-2
according to.

Mechanical properties

Minimum bending radius: 6 × cable diameter. Impact resistance: AG3, high stress level.

Environmental characteristics

Chemical and oil resistance: acceptable. UV resistant according to EN 50618.
Water resistance: AD6 (wave exposure).

Installation conditions

In the open air.
In conduit installed in bulkhead.
Installed in bulkhead.

STANDARDS

IN ACCORDANCE WITH STANDARDS
IEC 60092-353

STANDARDS AND APPROVALS
ABS / DNV-GL / BUREAU VERITAS / LLOYD’S
REGISTER /
CE / RoHS

More products in this series