TOXFREE® MARINE XZ1-K (AS) Marine power cable

Description

APPLICATIONS

Toxfree® Marine XZ1-K (AS) halogen-free cable is a safety cable. In case of fire, it does not release toxic or corrosive gases, which protects human health and prevents possible damage to electronic equipment. For this reason, its use is recommended for marine applications.

• For marine use.

• For public use.

STRUCTURE

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to standards EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene insulation (XLPE), type HF XLPE-90 °C, according to standard IEC 60092-360.

The standard identification of insulated conductors is as follows:

1 × natural

2 × blue + brown

3 × brown + black + grey

4 × brown + black + grey + blue

5 or more conductors: black, numbered

Other colors available on request.

Outer sheath

Low smoke halogen-free (LSHF) polyolefin sheath, type SHF1, according to standard IEC 60092-360. Black color.

Cross-section area (mm²) Diameter (mm) Weight (kg/km) Outdoor (A) Resistance at 20ºC (Ω/km) Voltage drop (V/A · km)
1 x 2.5 6,1 55 25 7,98 17,7
1 x 4 6,7 75 35 4,95 11,0
1 x 6 7,2 95 46 3,3 7,32
1 x 10 8,2 135 64 1,91 4,23
1 x 16 9,2 190 88 1,21 2,68
1 x 25 10,9 285 117 0,78 1,73
1 x 35 11,8 380 147 0,554 1,23
1 x 50 13,5 520 180 0,386 0,86
1 x 70 15,4 710 233 0,272 0,603
1 x 95 17,2 925 285 0,206 0,457
1 x 120 19,1 1.165 333 0,161 0,357
1 x 150 21,3 1.445 386 0,129 0,286
1 x 185 23,4 1.740 444 0,106 0,235
1 x 240 26,3 2.275 528 0,0801 0,178
1 x 300 29,1 2.870 612 0,0641 0,142
1 x 400 34,0 3.800 716 0,0486 0,108
1 x 500 37,7 4.855 823 0,0384 0,085
2 x 1.5 7,3 80 23 13,3 34,0
2 x 2,5 8,6 115 31 7,98 20,4
2 x 4 9,6 155 43 4,95 12,7
2 x 6 10,5 205 55 3,3 8,45
2 x 10 13,3 350 75 1,91 4,89
2 x 16 14,8 460 100 1,21 3,1
3 x 1.5 8,1 100 23 13,3 34,0
3 x 2.5 9,0 140 31 7,98 20,4
3 x 4 10,3 195 43 4,95 12,7
3 x 6 11,5 260 55 3,3 8,45
3 x 10 13,8 410 75 1,91 4,89
3 x 16 16,1 600 87 1,21 2,68
3 x 25 20,8 965 110 0,78 1,73
3 x 35 23,4 1.295 137 0,554 1,23
3 x 50 27,2 1.790 167 0,386 0,86
3 x 70 30,3 2.430 214 0,272 0,603
3 x 95 35,0 3.180 259 0,206 0,457
3 x 120 39,3 4.045 301 0,161 0,357
3 x 150 44,7 5.075 347 0,129 0,286
3 x 185 49,6 6.175 397 0,106 0,235
3 x 240 55,8 8.035 468 0,0801 0,178
4 x 1.5 9,0 125 20 13,3 29,5
4 x 2.5 9,8 170 28 7,98 17,7
4 x 4 11,5 245 37 4,95 11,0
4 x 6 12,8 325 47 3,3 7,32
4 x 10 15,5 520 65 1,91 4,23
4 x 16 18,2 770 87 1,21 2,68
4 x 25 23,4 1.225 110 0,78 1,73
4 x 35 25,2 1.625 137 0,554 1,23
4 x 50 30,1 2.270 167 0,386 0,86
4 x 70 35 3.150 214 0,272 0,603
4 x 95 40,3 4.160 259 0,206 0,457
4 x 120 44,6 5.210 301 0,161 0,357
4 x 150 49,7 6.510 347 0,129 0,286
4 x 185 55,2 7.910 397 0,106 0,235
4 x 240 62,1 10.300 468 0,0801 0,178
5 x 1.5 9,6 145 20 13,3 29,5
5 x 2.5 11,0 210 28 7,98 17,7
5 x 4 12,7 295 37 4,95 11,0
5 x 6 14,2 400 47 3,3 7,32
5 x 10 17,2 635 65 1,91 4,23
5 x 16 20,2 950 87 1,21 2,68
5 x 25 25,7 1.510 110 0,78 1,73
5 x 35 28,3 2.015 137 0,554 1,23
5 x 50 33,7 2.795 167 0,386 0,86
5 x 70 38,8 3.870 214 0,272 0,603
7 x 1.5 10,4 185 11 13,3 29,5
7 x 2,5 12,3 265 15 7,98 17,7
12 x 1,5 13,5 295 9 13,3 29,5
14 x 1.5 14,5 340 8,5 13,3 29,5
16 x 1,5 15,5 385 8 13,3 29,5
19 x 1.5 16,3 445 7,5 13,3 29,5
19 x 2.5 19,3 650 11 7,98 17,7
24 x 1,5 18,2 540 7 13,3 29,5
27 x 1.5 19,6 600 6,5 13,3 29,5

¹ Reference method F for single-core and method E for multicore cables according to IEC 60092-352 in open air at 45°C ambient temperature.

² At maximum service temperature and cosf=1. For cables having 2 conductors and 3 conductors up to 10 mm², it is supposed a single-phase circuit. For cables having more of 5 conductors is supposed that all are loaded. For the rest of the cables it is supposed a three-phase circuit.

More information

Electrical properties

Low voltage: 0.6/1 kV.

Thermal properties

Maximum operating temperature: 90 °C.
Maximum short-circuit temperature: 250 °C (max. 5 s).
Minimum installation temperature: -15 °C.
Minimum operating temperature: -40 °C (in fixed and protected installations).

Fire performance

No flame propagation according to standards EN 60332-1 / IEC 60332-1.
No flame propagation according to EN 60332-3-22 / IEC 60332-3-22 standards.
LSHF (Low Smoke Halogen Free) according to standards EN 60754-1 / IEC 60754-1.
Low smoke emission according to standards EN 61034 / IEC 61034:
light transmission > 60 %.
Low emission of corrosive gases according to standards EN 60754-2 / IEC 60754-2
according to.

Mechanical properties

Minimum bending radius:
≤ 25 mm: 4 × cable diameter
≥ 25 mm: 6 × cable diameter
Impact resistance: AG2, medium stress level.

Environmental characteristics

Chemical and oil resistance: good.
UV resistant according to standard EN 50618.
Water resistance: AD6 (wave exposure).

Installation conditions

In the open air.
In conduit installed in bulkhead.
Installed in bulkhead.

STANDARDS

According to standard
IEC 60092-353

Standards and approvals
ABS / DNV-GL / BUREAU VERITAS / LLOYD’S
REGISTER / CE / RoHS