OtsoSmart Logo White


Toxfree Marine Plus XOxTCuZ1-K (AS+)

Description

Purpose

Toxfree Marine Plus XOxZ1-K (AS+) and XOxTCuZ1-K (AS+) - halogen-free cables are safety, instrumentation and communication cables. They are fire resistant and specially designed for to continue data/signal transmission in case of fire. Therefore, their use is recommended for public spaces and marine applications.

• For marine use.

• For public use.

Construction

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), according to standard EN 60228 (conductor resistance according to standard IEC 60092-376, table 6).

Insulation

Mica tape + cross-linked polyethylene insulation, type HF XLPE 90 °C, according to standard IEC 60092-360.

The standard identification of insulated conductors is as follows: 2 × pair numbered

(white + blue).

Other colors available on request.

Strand assembly

Twisted conductors in pairs.

Single shielding (XO3Z1-K and XO3TCuZ1-K)

Aluminum + polyester tape with 100% coverage + tinned copper drain wire installed over assembled conductors.

Pair assembly

Twisted in concentric layers.

Total protection

Aluminium + polyester tape with 100% coverage + tinned copper drain wire installed over assembled pairs.

Braided shielding (XO2TCuZ1-K and XO3TCuZ1-K)

Tinned copper wire braid screen over common screen.

Outer sheath

Low Smoke Halogen Free (LSHF) thermoplastic polyolefin sheath, type SHF1, according to standard IEC 60092-360.

Orange color, non-toxic, flame retardant and fire resistant.

 

XO2TCuZ1-K (AS+)
Cross-section
(mm²)
Diameter
(mm)
Weight
(kg/km)
Outdoor
(A) 1
Resistance at 20ºC
(Ω/km)
1 x 2 x 0.75 8,3 100 17,1 27,6
2 x 2 x 0.75 11,6 145 13,7 27,6
4 x 2 x 0.75 14,9 215 11,2 27,6
7 x 2 x 0.75 20,1 335 9,2 27,6
10 x 2 x 0.75 22,5 495 8,6 27,6
14 x 2 x 0.75 23,7 585 7,4 27,6
19 x 2 x 0.75 26,5 745 6,5 27,6
24 x 2 x 0.75 31,3 945 6,5 27,6

 

XO3TCuZ1-K (AS+)
Cross-section
(mm²)
Diameter
(mm)
Weight
(kg/km)
Outdoor
(A) 1
Resistance at 20ºC
(Ω/km)
2 x 2 x 0.75 13,1 180 13,7 27,6
4 x 2 x 0.75 15,3 255 11,2 27,6
7 x 2 x 0.75 18,8 425 9,2 27,6
10 x 2 x 0.75 22,3 545 8,6 27,6
14 x 2 x 0.75 24,4 680 7,4 27,6
19 x 2 x 0.75 27,3 905 6,5 27,6
24 x 2 x 0.75 34,3 1.180 6,5 27,6

¹ Reference method E according to IEC 60092-352 and IEC 60364-5-52 in open air at 30°C ambient temperature.

For cables having more than 1 unit a factor is applied according to the Table A6 of the IEC 60092-352 standard

More information

Electrical properties

Instrumentation: 150/250 V.

Thermal properties

Maximum operating temperature: 90 °C.
Maximum short-circuit temperature: 250 °C (max. 5 s).
Minimum operating temperature: -40 °C (in fixed installations).
Minimum installation temperature: -15 °C.

Fire performance

No flame propagation according to standards EN 60332-1 / IEC 60332-1.
No fire propagation according to standards EN 60332-3-22 / IEC 60332-3-22
according to.
Fire resistant according to standards EN 60331-2 (overall diameter ≤ 20 mm) and IEC
according to 60331-1 (overall diameter > 20 mm).
LSHF (Low Smoke Halogen Free) according to standards EN 60754-1 / IEC 60754-1
according to.
Low smoke emission according to standards EN 61034 / IEC 61034:
light transmission > 60 %.
Low emission of corrosive gases according to standards EN 60754-2 / IEC
according to 60754-2.

Mechanical properties

Minimum bending radius:
≤ 25 mm: 4 × cable diameter
25 mm: 6 × cable diameter
Impact resistance: AG3, high stress level.

Environmental characteristics

Chemical and oil resistance: acceptable.
UV resistant according to standard EN 50618.
Water resistance: AD6 (wave exposure).

Installation conditions

In the open air.
In conduit, installed on bulkhead

STANDARDS

According to standard
IEC 60092-376

Standards and approvals
ABS / DNV-GL / BUREAU VERITAS / CE / RoHS